1.1. Overview Modern electrical power systems have three separate components - generation, transmission and distribution. Electrical power is generated at the power generating stations by alternators driven either by steam or hydro turbines. Most of the power generation takes place at generating stations that contain more than one alternator-turbine set. Depending upon the type of fuel used, the generating stations are categorized as thermal, hydro, nuclear etc. Most of the generating stations are located at remote regions. Hence the electric power generated at a generating station has to be transmitted over a long distance to load centers which are usually cities or towns. This is called the power transmission. In fact, power transmission towers and transmission lines are very common …show more content…
Electrical Faults THE control of grid-connected voltage source inverters (VSIs) under unbalanced voltage sags has been widely addressed in the technical literature. Some research has focused on active power control strategies, and two methods have been presented to provide the current references for the VSIs [1], [2]. As in the case of synchronous generators in conventional power plants, VSIs should remain connected during voltage sags and support the grid voltages with the injection of reactive currents [3], [4]. This is necessary to ride-through any type of fault. In electrical power systems consisting of generators, transformers, transmission lines and distribution circuits, most of the faults, about two-thirds, are liable to occur in the transmission lines. A fault in a circuit is any failure which interfaces with the normal flow of current. The faults occur in power system due to insulation failure of equipments, flashover of lines initiated by a lightning stroke, due to permanent damage to conductors and towers or due to accidental faulty operations. The faults can be broadly classified into shunt faults (short circuits) and series faults(open
• Then the fault cable is tested to determine the type of fault, 18 KV is applied on each phase for 5 minutes, if the phase can carry this voltage, so this phase is good and no fault on it, if the phase cannot withstand this value of voltage, this means that the insulation is damaged and this phase is faulty, If one or more phase cannot withstand the 18 KV then these phases are faulty and the type of fault is short circuit due to breakdown of the insulation, but if the phases withstand the 18 KV applied but the current from the sending end not reach the other end, this means that there is an open circuit fault which is may be break in the conductor or the joint connecting the
When the fault happens, the high currents pass though the lines depending on their impedances to provide the fault what needs. As shown in Fig. 3 and Fig. 4, the power flow in all buses (bus 1 is blue, bus 2 is red, bus 3 is black, and bus 4 is green) would be changed after the circuit breakers resulting in change the configuration of the system. The spike of power flow in this test system at clearing time is caused by the switching of circuit breakers of Line 2 to off-line and
Experiment 7 In this experiment we configured several DC circuits consisting of an emf and a network of resistors. The circuits were composed of a power supply, two DMMs, a circuit board, an SPST switch, and an assortment of known resistors along with one unknown resistor. We measured the current and voltage of the entire circuit as well as the potential drops across each resistor to determine the parameters of the circuit including the resistance, voltage, and current for each component.
Existing basic unit is shown in fig.2.1. As shown in fig.2.1, the basic unit consist of three dc voltage sources and five unidirectional power switches. In this structure, power switches (S_2,S_4),(S_1,S_3, S_4, S_5), and (S_1,S_2,S_3, S_5) should not be simultaneously turned on in order to protect the dc voltage sources from the short circuit. Table 2.1 shows the existing basic unit power switches turn on and off states, where the basic unit is able to generate three different voltage levels at the output that is 0, V_1+V_3, and V_1+V_2+V_3. It is important to note that the basic unit is only able to generate positive levels at the output.
7.4.1.1 Dielectric withstanding voltage The purpose of this test is to prove that a connector can operate safely at its rated voltage and will be able to withstand momentary over potentials due to switching, surges and other similar phenomena. The applied voltage can be either AC or DC. The voltage should be applied across the two closely spaced contacts as well as between a connector shell and the contacts closest to the shell. The test voltage in the case of coaxial connectors shall be applied between the inner and outer conductor. The voltage should be ramped up uniformly from zero to rated value.
In this control system, sub-stations are work separately and all are connect to each other through grid system. If any sub-system's control system is shuts so in that case that sub-system area will effected. In addition, no need to shut whole system. In addition, if the fault is big so in that case that area power supply will start through another sub-station via grid system. Figure: decentralized system architecture
The testing of the linear WEC was split into three main sections the first being electrical/electronic systems, the second being mechanical systems and finally complete system tests. 5.2 Electrical and Electronic Tests and Results 5.2.1 Preliminary Test Conditions Schematic Check
UET 30612 • Cert III in ESI - POWER SYSTEMS DISTRIBUTION CABLE JOINTING QUALIFICATION UET3018 • UETTDRRF11A TESTING OF CONNECTIONS TO LOW VOLTAGE ELECTRICITY NETWORKS • SERVICE CONNECTION TESTING METREL POLARITY PLUS (WESTERN POWER) • WESTERN POWER HIGH VOLTAGE INSULATOR WASHING CERTIFICATE • SWITCHING AUTHORIZATION UP TO AND INCLUDING 33KV (ZIMBABWE)
In addition, excessive rainwater has caused damage to the weight-bearing pillars that are holding up the house. Inside the house, there are faulty electrical connectors and exposed electrical lines that can lead to a potential electric shock. The entirety of the house also contains
The broken windows theory was initiated from the idea of “order maintenance”. Order maintenance gave off the impression that the community was not the authority in control, but that it tolerated minuscule actions that encourage more serious and more violent crimes. The adoption of the broke windows theory made way for the zero tolerance policy, which simply states that no matter what the circumstances are, when it comes to crimes within the streets and discipline in the schools, punishment will be applied. The broken windows theory is used as a signaling effect of urban disorder and vandalism on anti-social behavior and any other additional crimes. The theory expresses that while maintaining and keeping a watch over urban environments to help
There's a lot of buzz going on about electric cars and it seems like every hipster and eco nut trying to save the environment but do you truly know what it takes to get them on the road. The process to make the batteries is a truly dirty process and it pollutes the air. Most electric cars that are available to the general public are very expensive and most of them do not have a very far range. Somewhere between a 20-270 mile range. Also you need to live somewhere there are the charging stations or have one put in at your home.
INTRODUCTION A smart grid is a power network which is based on digital technology is used to supply power, via two-way digital communications. A smart grid system allows for monitoring, analysis, control and communication within the supply chain and helps improve efficiency, reduce energy consumption and cost, and maximize the transparency and reliability of the energy supply chain. The smart grid was introduced with the aim of overcoming the weaknesses of conventional electrical grids by using smart meters.
Earthquakes are caused when rock underground suddenly breaks along a fault. This sudden release of energy causes the seismic waves that make the ground shake. When two plates are rubbing against each other, they stick a little. Most earthquakes occur along the edge of the oceanic and continental plates. Due to stress they shift and cause the earthquake.
Every human being has their own career aspirations and mine is to be a Electrical engineer, a dream that I held ever since I was in school due to my deep interest in technical fields such as electrical and electronics. Although, electrical engineer is a difficult career to achieve because it have many obstacles and challenges to be met, but I am sure that I am able to make full preparations for the realization of my dreams. The main preparation I need to prepare is knowledge. Knowledge in Electrical engineering is essential in order for me to become a successful engineer as I am required to be able to identify, study and solve the problem that I encountered in implementing the knowledge that I have gained in university.
Social Problems in Societies Social problems are issues which are considered to affect majority if not all members of a society either directly or indirectly. Whenever people come to live together in a social setting, conflict arises from their differences in opinions regarding political issues, religion, ethnic issues, cultural practices and other health and hygiene issues. In such a situation, we can say a society inevitably develops social problems. The various social issues present today vary from society to society, and as such, we cannot say that all societies face similar social issues.